Regeneration Excess Alarm
Fanuc · Macro B CNC Programming
Hva betyr 08 ?
This alarm occurs in the αi PSR (Power Supply, Resistance Discharge Type) when a spindle motor with a maximum output of 5kW or more is decelerated while an inappropriate 16Ω regenerative discharge unit is used. The unit cannot dissipate the excess regenerative energy.
Vanlige årsaker
- Excessive energy is being regenerated back into the system.
- Regeneration braking torque exceeds system capacity.
- Control system unable to dissipate regenerated energy.
- Faulty braking resistor or chopper circuit.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the maximum output of the spindle motor. If it is 5kW or more, the regenerative discharge unit resistance must be 8Ω, not 16Ω.
- 2
Check the installed regenerative discharge unit (refer to Section 3.1.3.8, page 93, for ordering numbers). If it is a 16Ω unit (e.g., A06B-6089-H510, A06B-6089-H500, A06B-6089-H713) and the motor is 5kW or more, replace it with an 8Ω unit (e.g., A06B-6089-H711 or A06B-6089-H712).
- 3
Ensure the forced cooling fan of the regenerative discharge unit (if applicable, e.g., H7xx series units on page 93) is fully operational.
- 4
Review the spindle motor deceleration parameters in the CNC. Adjust them to reduce the regenerated energy if hardware replacement is not immediately feasible.
- 5
Confirm that the spindle deceleration is not excessively rapid or frequent, which could generate high regeneration energy spikes that exceed the unit's capacity.