301
Serial Pulse Coder Communication Error (CRCER)
Fanuc · Alpha i series AC Servo Motor
Hva betyr 301 ?
A communication error (CRCER) was detected for the serial pulse coder, indicating a data integrity issue during serial communication. Potential causes include cable faults, component defects, or external noise.
Vanlige årsaker
- Discontinuity or damage in the serial pulse coder signal cable.
- Defective serial pulse coder.
- Defective servo amplifier module.
- External electrical noise interfering with serial communication.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the continuity and integrity of the serial pulse coder signal cable.
- 2
If the cable is verified as normal, replace the pulse coder or the servo amplifier module.
- 3
Implement noise reduction measures as described in the 'Descriptions' chapter on noise.