Oversetter...
SP0139
Pulse Error Alarm
Fanuc · Alpha i Series AC Servo Motor and Spindle
Hva betyr SP0139 ?
An error occurred in the interpolation circuit of the spindle control system. This typically indicates an issue with the feedback signal processing, leading to inaccurate position or speed control.
Vanlige årsaker
- Incorrect or missing pulse signal from an encoder or other pulse-generating device.
- Encoder damage or misalignment causing intermittent pulse output.
- Noise or electrical interference affecting the pulse signal integrity.
- Pulse counting error due to excessive speed or data rate.
- Parameter settings for pulse input (e.g., P4-xx) are incorrect.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the integrity of the pulsecoder feedback cable (e.g., K22 for SV, K16/K97 for SP).
- 2
Check for electrical noise interference on the feedback lines.
- 3
Inspect the pulsecoder for physical damage or misalignment.
- 4
If the sensor head was moved, perform interpolation error learning according to Subsection 11.2.3.9.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Fanuc Alpha i Series AC Servo Motor and Spindle