Oversetter...
SP0012

DC Link Overcurrent / IPM Alarm

Fanuc · AC Spindle Motor Alpha i-Beta i Series Parameters

Hva betyr SP0012 ?

An overcurrent condition is detected in the DC link of the converter, or an alarm is issued by the IPM (Intelligent Power Module). This usually indicates a short circuit in the motor, power module failure, or sudden high load.

Vanlige årsaker

  • Short circuit in the motor or motor cabling.
  • Faulty IPM (Intelligent Power Module) in the spindle amplifier.
  • DC link capacitor failure.
  • Overload condition causing excessive current draw.
  • Ground fault in the motor or power leads.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the resistance between motor phases (U, V, W) and ground.

  2. 2

    Inspect the spindle motor power cables for signs of damage or insulation breakdown.

  3. 3

    Check the DC link voltage (P+, P-) for stability under load.

  4. 4

    Verify that the braking resistor circuit is functioning correctly.

  5. 5

    Run a low-speed motor test while monitoring DC link current.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Fanuc AC Spindle Motor Alpha i-Beta i Series Parameters