Oversetter...
4

Earth Fault

Danfoss · VLT Micro Drive FC 51

Hva betyr 4 ?

An earth fault (ground fault) has been detected in the motor or the cabling between the drive and the motor. This indicates current leakage to ground, which is a serious safety hazard and can cause significant damage to the drive or motor if not resolved promptly.

Vanlige årsaker

  • Degraded insulation in the motor windings due to age, moisture ingress, or mechanical stress.
  • Damage to the motor cable insulation (e.g., crushing, abrasion, chemical exposure) creating a path to ground.
  • Water or conductive dust ingress into the motor terminal box or drive output terminals (U, V, W).
  • Incorrectly grounded motor frame or cabinet, leading to stray current paths.
  • Leakage current from output filter components if a non-standard filter is used.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Disconnect the motor cables from the drive's output terminals (U, V, W) and then power cycle the drive to see if the fault clears.

  2. 2

    Perform an insulation resistance test (Megger test) on the motor windings to earth (motor frame) with a 500VDC Megger, expecting >1 Megaohm.

  3. 3

    Perform an insulation resistance test on each motor cable phase (U, V, W) to earth along the entire cable run with a 500VDC Megger.

  4. 4

    Visually inspect the motor terminal box for moisture, corrosion, or signs of arcing.

  5. 5

    Check continuity between the motor frame and the main earthing point of the control cabinet.

Se alle koder i denne manualen (51)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Danfoss VLT Micro Drive FC 51