3

No motor

Danfoss · VLT AutomationDrive FC 301/302

Hva betyr 3 ?

No motor is connected to the output of the frequency converter. This indicates an open circuit condition on the motor output terminals.

Vanlige årsaker

  • Motor cable severed or disconnected from the drive output terminals (U, V, W) or the motor terminal box.
  • Internal open circuit in one or more motor windings (e.g., due to thermal overload, insulation breakdown).
  • Loose or corroded electrical connections on the motor terminal block or the drive's output terminals.
  • External motor protection device (e.g., thermal overload relay, contactor) tripped or faulty, interrupting power.
  • Incorrect motor cable sizing or severe cable damage causing high resistance or an open circuit.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Safely de-energize the drive and motor. Verify all physical connections from the drive output (U, V, W) to the motor terminal box.

  2. 2

    Measure the resistance between each pair of motor output terminals at the drive (U-V, V-W, W-U); all should be equal and low impedance (e.g., <1 Ohm).

  3. 3

    Measure the insulation resistance of the motor windings to ground using a megohmmeter (e.g., 500VDC test, expected >1MOhm).

  4. 4

    Disconnect the motor cables from the motor terminal box and measure the resistance of each motor winding (U-V, V-W, W-U) directly at the motor.

  5. 5

    Inspect any motor contactor or starter (if present) for proper operation, ensuring all main contacts close when commanded.