Oversetter...
2821

Serial port overflow

Danfoss · VLT AutomationDrive FC 301/302

Hva betyr 2821 ?

The serial port buffer has overflowed, indicating that data is being received faster than it can be processed. This can lead to loss of communication or corrupted data.

Vanlige årsaker

  • Data being transmitted to the serial port (e.g., RS-485, RS-232) at a baud rate higher than the drive's processing capability.
  • Excessive, unsolicited communication messages from a connected master device.
  • Software bug in the drive's serial communication handler failing to process incoming data quickly enough.
  • High processor load within the drive diverting resources from serial communication tasks.
  • Intermittent noise on the serial lines corrupting data and causing re-transmission attempts that fill the buffer.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Reduce the baud rate of the connected master device to match P8-10 (Baud rate) or a lower, more stable rate.

  2. 2

    Verify Parameter P8-11 (Protocol) is correctly configured for the connected device (e.g., FC Protocol, Modbus RTU).

  3. 3

    Check the integrity of the serial communication cable for proper shielding and verify termination resistors are correctly installed.

  4. 4

    Monitor the communication traffic using a protocol analyzer to identify if an external device is sending excessive data.

  5. 5

    Update the drive firmware to the latest available version to address potential communication handler bugs.

Se alle koder i denne manualen (66)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Danfoss VLT AutomationDrive FC 301/302
Danfoss 2821 Serial port overflow: Serviceinformasjon | ErrorLib