Option software in slot B not supported/allowed
Danfoss · VLT AutomationDrive FC 301/302
Hva betyr 1316 ?
The software installed on the option card in slot B is not compatible or permitted for use with the current drive configuration. This prevents proper integration and functionality of the option.
Vanlige årsaker
- Incorrect option card type installed in Slot B for the specific drive model or application.
- Firmware on the option card in Slot B is of an incompatible type or version that is explicitly disallowed by the drive's main firmware.
- A custom firmware version on the option card in Slot B is incompatible with the standard drive platform.
- Configuration parameter (e.g., P14-41 Option B type) is set incorrectly for the installed hardware.
- Corruption during a firmware update process on the option card in Slot B, leading to an unsupported state.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Verify the part number and type of the option card physically installed in Slot B.
- 2
2. Cross-reference the installed option card's part number against the drive's documentation to ensure it is a compatible accessory for the specific drive model.
- 3
3. Check the firmware version of the option card in Slot B (e.g., P15-06) and compare it against the drive's compatibility list for supported versions.
- 4
4. Ensure that relevant configuration parameters for Slot B (e.g., P14-41) are set to correctly reflect the installed option card type.
- 5
5. If the option card is verified compatible but still errors, attempt to update the option card's firmware to the latest official version via a dedicated tool.