850
SERCOS: Repeated message failure.
Bosch Rexroth · Motion Control
Hva betyr 850 ?
Two successive drive telegrams from the same address have failed, causing the NC to automatically switch back to SERCOS phase 0. This is a servo loop or drive fault, indicating persistent communication problems on the SERCOS network.
Vanlige årsaker
- Failure of two successive drive telegrams from the same SERCOS address.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the SERCOS configuration for correctness.
- 2
Verify the integrity and connections of SERCOS cables.
- 3
Inspect all drives connected to the SERCOS ring for faults.
- 4
Initiate a new SERCOS startup.