F2816

Softstart fault power supply unit

Bosch Rexroth · IndraDrive Troubleshooting

Hva betyr F2816 ?

During the soft start process, which involves loading the DC bus capacitance, the DC bus voltage curve is monitored. Significant deviations from the expected curve suggest a defect in the power section of the HMV01 supply unit. This fault indicates a problem specifically during the initial power-up sequence.

Vanlige årsaker

  • Short circuit in DC bus.
  • Load on DC bus (e.g., external braking resistor incorrectly connected).
  • Insulation error in DC bus wiring or within the device/other connected devices.
  • Final DC bus voltage not reached within a maximum time.
  • Inadmissible voltage fluctuations or drop in supply mains during soft start.
  • Device defective.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check DC bus wiring for short circuits and remove any found.

  2. 2

    Check DC bus wiring for load; verify correct connection of any external braking resistor.

  3. 3

    Check DC bus wiring for insulation errors; if wiring is correct, systematically remove connected devices from the drive system step by step to identify the defective device.

  4. 4

    Check for defects at loads externally connected to the DC bus.

  5. 5

    Check mains voltage for inadmissibly dropped values during soft start.

  6. 6

    Replace the device.