F2010

Error when initializing digital inputs/outputs

Bosch Rexroth · IndraDrive Troubleshooting

Hva betyr F2010 ?

An error occurred during the drive's initial startup sequence, specifically during the initialization of the digital inputs and outputs. This indicates a configuration conflict or issue with the I/O parameters.

Vanlige årsaker

  • Conflict with last stored parameters of digital inputs/outputs.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check parameter P-0-0300 (Digital I/Os, assignment list) and correct if necessary.

  2. 2

    Check parameter P-0-0301 (Digital I/Os, bit numbers) and correct if necessary.

  3. 3

    Check parameter P-0-0302 (Digital I/Os, direction) and correct if necessary.

Se alle koder i denne manualen (16)
Verifisert teknisk data. Sist oppdatert: March 2026