Safety rel. position limit val., exc. in pos. dir.
Bosch Rexroth · IndraDrive MPx02
Hva betyr F7011 ?
This safety technology error indicates that the motor's actual position has exceeded the safety-related positive position limit value configured in the IndraDrive MPx02. This is a critical safety violation, implying the machine has moved beyond its safe upper boundary, requiring an immediate safety stop.
Vanlige årsaker
- Incorrectly set safety-related positive position limit (e.g., S-0-0193) in the IndraDrive MPx02.
- Encoder counting error or offset, leading to incorrect actual position reporting.
- Loss of control or unexpected motion command pushing the axis beyond the limit.
- Mechanical overrun due to inertia or external forces.
- Faulty safety limit switch or sensor that failed to activate or register.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Review and adjust the safety-related positive position limit parameter (e.g., S-0-0193 'Safety related position limit positive') in the IndraDrive MPx02, ensuring it is correct for the machine's physical limits.
- 2
Verify the motor encoder for accurate position feedback. Check for mechanical slippage, loose couplings, or encoder damage.
- 3
Inspect any external positive travel limit switches or sensors and their wiring for proper function and connection.
- 4
Check the commanded motion profile and ensure that no trajectory attempts to exceed this limit.
- 5
Perform a re-referencing or recalibration of the axis position, if applicable.