Safety command for system start incorrect
Bosch Rexroth · IndraDrive MPx02
Hva betyr F3150 ?
This non-fatal safety error indicates that the command received by the IndraDrive MPx02 to initiate a safety-related system start is incorrect or invalid. This typically prevents the drive from transitioning from a safe stopped state to an operational state, maintaining the safety shutdown.
Vanlige årsaker
- Incorrect sequence or timing of the safety start command from the master controller or safety PLC.
- Mismatch between the expected and received safety start command (e.g., wrong bit pattern or value).
- Communication error preventing the correct safety start command from reaching the IndraDrive MPx02.
- Incorrect parameterization of the safety start logic.
- Preconditions for safety system start (e.g., E-stop reset, guards closed) are not met.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the exact sequence, timing, and value of the safety system start command being sent by the master controller or safety PLC.
- 2
Check safety parameters in the IndraDrive MPx02 related to safety start logic and enable conditions.
- 3
Ensure that all necessary preconditions for a safety system start (e.g., E-stop reset, safety guards closed, acknowledgment given) are met.
- 4
Inspect the communication link between the master controller and the IndraDrive MPx02 for errors.
- 5
Refer to the IndraDrive MPx02 safety manual for the precise system start procedure and required command structure.