Contactor control error
Bosch Rexroth · IndraDrive MPx02
Hva betyr F2834 ?
An error has occurred in the control circuit for a contactor, typically the mains contactor or a motor contactor. This implies that the drive commanded the contactor to switch, but the feedback signal indicated a discrepancy (e.g., contactor failed to close/open, or opened unexpectedly). This can compromise safety or prevent motor operation.
Vanlige årsaker
- Defective contactor coil or auxiliary contacts
- Faulty wiring to the contactor coil or feedback contacts
- Insufficient control voltage for the contactor coil
- Incorrect feedback signal from the contactor
- Internal drive output stage fault for contactor control
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Inspect the mains or motor contactor (if present) for mechanical integrity, visible damage, and smooth operation of contacts.
- 2
Verify all wiring connections to the contactor coil and auxiliary feedback contacts for proper termination and tightness.
- 3
Measure the control voltage at the contactor coil terminals when the drive attempts to engage the contactor, comparing it to the nominal coil voltage specification.
- 4
Measure the feedback signal voltage from the contactor auxiliary contacts at the drive input terminals to confirm correct state change corresponding to contactor operation.
- 5
Check the drive parameters related to contactor control, feedback monitoring, and delay times for correct configuration according to the system documentation.