Oversetter...
E8026
Undervoltage in power section
Bosch Rexroth · IndraDrive C Drive Controllers
Hva betyr E8026 ?
The DC bus voltage in the drive's power section has dropped below the minimum acceptable threshold. This indicates insufficient power available for motor operation.
Vanlige årsaker
- Insufficient incoming AC mains voltage (see E2814).
- Excessive load causing a momentary drop in DC bus voltage.
- Faulty rectifier stage or pre-charge circuit in the drive.
- Internal power supply issue within the drive.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the incoming AC mains voltage at the drive's input terminals and ensure it is stable and within specified limits.
- 2
Check the DC bus voltage at the +UDC/-UDC terminals on the drive during operation and ensure it remains above the undervoltage threshold.
- 3
Verify that the drive is correctly sized for the motor and application load, avoiding momentary overloads.
- 4
Inspect the pre-charge resistors and contactors/relays for proper functionality if the fault occurs during power-up.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Bosch Rexroth IndraDrive C Drive Controllers