Undervoltage in mains
Bosch Rexroth · IndraDrive C Drive Controllers
Hva betyr E2814 ?
The incoming AC mains voltage is below the acceptable operating threshold for the drive's power section. This can lead to insufficient DC bus voltage and operational issues.
Vanlige årsaker
- Incoming AC supply voltage sag or brownout.
- Incorrect mains voltage setting in drive parameters for the actual supply.
- Loose or high-resistance connections in the mains power circuit.
- Overloaded mains supply causing voltage drop.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the incoming AC mains voltage at the drive's input terminals and verify it is within the drive's specified operating range.
- 2
Check all connections in the mains power circuit, including circuit breakers, contactors, and terminal blocks, for tightness and corrosion.
- 3
Verify the mains voltage parameter setting in the drive configuration matches the actual incoming supply voltage.
- 4
Monitor the mains voltage over time to detect transient sags or brownouts, especially during peak load conditions.