E2058

Selected process block is not programmed.

Bosch Rexroth · IndraDrive C Drive Controllers

Hva betyr E2058 ?

The drive controller was commanded to execute a process block that does not exist or has not been programmed into its memory. This prevents the execution of the requested motion sequence.

Vanlige årsaker

  • A non-existent or unprogrammed process block number was selected for execution.
  • Programming error in the motion sequence referring to an incorrect block number.
  • Memory corruption or data loss in the drive's program storage.
  • Incorrect program loaded into the drive controller.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the process block number being called in the motion program or HMI and ensure it corresponds to an existing, programmed block.

  2. 2

    Check the drive's program memory for the presence and integrity of the process blocks.

  3. 3

    Reload the correct application program into the drive controller if there is suspicion of data corruption.

  4. 4

    Consult the machine documentation to confirm the correct process block numbers and their functions.