Oversetter...
FB MON Bit 1

Monitoring Discrepancy Error - Input Group 2

Beckhoff · TwinSAFE Logic FB

Hva betyr FB MON Bit 1 ?

A discrepancy has been detected between the channels of input group 2 in the FB MON function block. This means the redundant inputs are not switching in sync or are reporting different states, indicating a potential sensor fault, wiring issue, or incorrect timing that could compromise the monitoring function, leading to a safety stop.

Vanlige årsaker

  • One channel of the redundant safety input device for Group 2 is experiencing an intermittent connection or contact failure.
  • Damaged insulation or a short to an adjacent wire on one input channel (e.g., MonIn_CH2_2) of the monitored device.
  • Physical obstruction or wear preventing proper actuation of the safety device's redundant contacts.
  • Safety controller's internal input filtering for Group 2 is inadequate, allowing noise to be interpreted as a discrepancy.
  • Parameter (e.g., P_MON_CONFIG_G2) setting for input logic (e.g., NO/NC) for Group 2 is incorrect.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Observe the diagnostic status of both Input Group 2 channels (e.g., via software or LEDs IN_G2_A, IN_G2_B) while actuating the monitored safety device.

  2. 2

    Measure the voltage potential on both input terminals (e.g., X11.1 and X11.2) of the safety controller for Group 2, relative to ground.

  3. 3

    Verify the wiring integrity from the monitored device's output contacts to the safety controller's Input Group 2 terminals.

  4. 4

    Adjust the discrepancy monitoring time (e.g., P_MON_DISCREPANCY_WINDOW_G2) in the safety controller to accommodate slight timing differences.

  5. 5

    Inspect the monitored safety device itself (e.g., safety light barrier, gate switch) for physical damage, misalignment, or contamination.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder