Oversetter...
00ED

Invalid block-transfer request size

Allen-Bradley · Logix 5000

Hva betyr 00ED ?

The size of the block-transfer request is not consistent with valid block-transfer size requirements. This indicates an incorrect payload size for the transfer operation.

Vanlige årsaker

  • The size of the block-transfer request is not consistent with valid block-transfer size requests

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect the Logix 5000 controller's fault log to identify the specific routine and block-transfer instruction (e.g., MSG instruction) generating the 'Invalid block-transfer request size' fault.

  2. 2

    Verify the 'Element Count' or 'Length' parameter configured within the identified block-transfer instruction against the intended data payload size.

  3. 3

    Compare the data structure and size (e.g., array dimensions, data type) of the target tag or device/module in the remote system with the size expected by the Logix 5000 block-transfer instruction.

  4. 4

    Review the starting address and length parameters within the block-transfer instruction to ensure they do not attempt to read or write beyond the defined boundaries of the source or destination data object.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026