Overvoltage

Allen-Bradley · PowerFlex 700

Hva betyr 5 ?

The DC bus voltage has exceeded its maximum permissible value. This can be caused by high incoming AC line voltage, transient voltage spikes, or regenerative energy from a decelerating motor, risking damage to the drive's DC bus capacitors.

Vanlige årsaker

  • DC bus voltage exceeds the overvoltage limit.
  • Regenerative braking energy is not being dissipated effectively.
  • Input line voltage is too high.
  • Faulty braking chopper or resistor (if applicable).

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Monitor the incoming AC line voltage for high voltage conditions or transient spikes.

  2. 2

    Extend the deceleration time (e.g., by increasing the deceleration ramp parameter).

  3. 3

    Install a dynamic brake option (resistor and chopper circuit) to dissipate regenerative energy.