0035
ILLEGAL INSTRUCTION IN INTERRUPT FILE
Allen-Bradley · MicroLogix 1400 Programmable Controllers
Hva betyr 0035 ?
The program contains a Temporary End (TND), Refresh (REF), or Service Communication instruction within an interrupt subroutine (STI, EII, HSC) or a user fault routine. These specific instructions are not permitted in interrupt contexts due to their system-level implications or timing characteristics. This is a nonrecoverable fault.
Vanlige årsaker
- Unsupported instructions (TND, REF, Service Communication) are placed inside an interrupt service routine (STI, EII, HSC) or user fault routine.
- Incorrect programming practices for interrupt service routines, violating execution rules for these contexts.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Correct the program by removing Temporary End (TND), Refresh (REF), or Service Communication instructions from all interrupt subroutines (STI, EII, HSC) and user fault routines.
- 2
Recompile and reload the modified program into the controller.
- 3
Enter the Run mode after the program is successfully reloaded.
Verifisert teknisk data. Sist oppdatert: March 2026