0002
Unexpected Reset
Allen-Bradley · MicroLogix 1400 Programmable Controllers
Hva betyr 0002 ?
The controller experienced an unexpected reset, possibly due to electrical noise in the environment or an internal hardware malfunction. Consequently, the default program has been loaded, indicating a loss of the previously loaded user program.
Vanlige årsaker
- Controller reset due to a noisy operating environment.
- Internal hardware failure within the controller.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Review and implement proper grounding guidelines as described in the controller User Manual.
- 2
Install surge suppressors according to guidelines in the controller User Manual.
- 3
Verify that the battery is connected to the controller.
Verifisert teknisk data. Sist oppdatert: March 2026