F016

Scanner Not Available to 1771 Rack Adapter

Allen-Bradley · Logix and SLC PLC

Hva betyr F016 ?

This fault occurs when the communication scanner is unable to establish or maintain communication with a 1771 rack adapter. This prevents I/O modules in the 1771 rack from being read or written to.

Vanlige årsaker

  • Physical disconnection of the scanner from the 1771 rack adapter.
  • 1771 rack adapter power failure or hardware fault.
  • Incorrect configuration of the scanner or adapter module.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify power supply voltage to the 1771 rack adapter and the 1771 I/O rack backplane against specified nominal values.

  2. 2

    Inspect all communication cabling between the communication scanner module and the 1771 rack adapter for damage, proper termination, and secure connections.

  3. 3

    Check status indicators (e.g., COM, OK, FAULT LEDs) on both the communication scanner module and the 1771 rack adapter for diagnostic information.

  4. 4

    Verify the communication parameters and addressing configured in the PLC's scanner module match the physical DIP switch settings or configuration of the 1771 rack adapter.