Allen-Bradley Compact 5000 I/O Serial Module
28 feilkoder dokumentert
Recoverable Module Fault / Firmware Update Issue / Connection Timeout
A flashing red module status indicator points to one of several conditions: a module firmware update in progress, a failed firmware update attempt, a recoverable fault, or a connection timeout to the module. This state implies an issue that may be resolved without module replacement, often through software intervention or power cycling. It requires investigation to determine the specific root cause.
Generic ASCII Channel Data Fault
This boolean tag indicates that the channel data for the Generic ASCII protocol is inaccurate and cannot be trusted by the application. A value of 1 (Bad) signifies an active fault condition within the module or its communication specific to the ASCII channel. The tag automatically resets to 0 (Good) once the condition causing the inaccuracy is removed.
DF1 Connection Faulted
This boolean tag indicates the operational status of the DF1 connection for module 'x'. When the module successfully establishes and maintains a connection, the tag value is 0. If the connection to the DF1 device is lost or was never established, this tag transitions to 1, signaling a connection failure, which can be a major or minor fault depending on controller configuration (page 77).
DF1 Diagnostic Active
This boolean tag for module 'x' indicates that one or more diagnostic conditions are currently active or that a prognostic threshold has been reached within the DF1 channel. A value of 1 signifies an ongoing diagnostic event, which means a problem or potential problem exists, requiring further investigation to identify the specific issue.
DF1 Diagnostic Sequence Count
This SINT tag for module 'x' increments each time a unique diagnostic condition is detected or transitions from active to inactive on the DF1 channel. It acts as a change counter for diagnostic states, providing a means to track the frequency and occurrence of diagnostic events. The count resets to zero upon product reset or power cycle, and wraps from 255 (-1) to 1, skipping zero.
DF1 Master Normal Poll Error
This boolean tag for DF1 Master module 'x' indicates that an error occurred during a normal polling cycle. A value of 1 signifies that the normal poll did not complete successfully, affecting routine data acquisition from standard slave devices on the DF1 network.
DF1 Master Poll Group Size Error
This boolean tag for DF1 Master module 'x' indicates a configuration error where the defined Normal Poll Group size exceeds the maximum allowable number of nodes for normal polling. A value of 1 signifies that the polling configuration is invalid and cannot be executed as specified, leading to polling failures for normal nodes.
DF1 Master Priority Poll Error
This boolean tag for DF1 Master module 'x' indicates that an error occurred during a priority polling cycle. A value of 1 signifies that the priority poll did not complete successfully, potentially disrupting critical, time-sensitive data exchange with a high-priority slave device.
Modbus Slave Buffer Overrun
This boolean tag indicates that a buffer overrun occurred within the Modbus slave module's ASIC (Application-Specific Integrated Circuit) during data reception. A value of 1 (Occurrence) means the slave's receive buffer overflowed because incoming data arrived too quickly to be processed. This condition can lead to data loss and unreliable slave operation.
Modbus Slave CRC/LRC Error
This boolean tag indicates that a CRC (Cyclic Redundancy Check) or LRC (Longitudinal Redundancy Check) error occurred during Modbus slave communication. A value of 1 (Occurrence) means that the received Modbus message failed its integrity check, suggesting data corruption during transmission. This indicates an issue with the physical layer or data format.
Modbus Slave Channel Data Fault
This boolean tag indicates that the channel data for the Modbus slave is inaccurate and should not be trusted for use in the application. A value of 1 (Bad) signifies an active fault condition originating from the slave's operation or data processing. The tag automatically resets to 0 (Good) once the condition causing inaccuracy is removed.
Modbus Slave Framing Error
This boolean tag indicates that a framing error occurred during data reception by the Modbus slave module. A value of 1 (Occurrence) means the received data did not conform to the expected Modbus frame structure. This often points to baud rate, data bits, or stop bits mismatches between the master and slave, leading to communication failure.
Modbus Slave Illegal Data Address
This boolean tag indicates that the Modbus master requested access to a Modbus register address that is outside the valid range defined for the slave module. A value of 1 (Occurrence) means the slave received a request for a memory location it does not support. This prevents the slave from fulfilling the master's request.
Modbus Slave Parity Error
This boolean tag indicates that a parity error occurred during Modbus slave communication. A value of 1 (Occurrence) means a data transmission error was detected due to incorrect parity. This suggests corruption in the serial data stream received by the slave, leading to unreliable data processing.
Modbus Slave Channel Data Uncertain
This boolean tag indicates that the channel data for the Modbus slave might be inaccurate, with an unknown degree of unreliability. A value of 1 (Uncertain data) suggests potential issues with data integrity, though not a definitive fault. The tag automatically resets to 0 (Good data) once the condition causing uncertainty is removed.
Modbus Master Command Buffer Overrun
This boolean tag indicates that a buffer overrun occurred during data reception for a specific Modbus master command (Command yy). A value of 1 (Occurrence) means the module's receive buffer overflowed because data arrived faster than it could be processed. This condition can lead to data loss and unreliable command responses.
Modbus Master Command Data Fault
This boolean tag indicates that the data related to a specific Modbus master command (Command yy) is inaccurate and should not be trusted by the application. A value of 1 (Bad) signifies an active fault condition associated with the command execution or its resulting data. The tag automatically resets to 0 (Good) when the fault condition is resolved.
Modbus Master Command Framing Error
This boolean tag indicates that a framing error occurred during the reception of a response for a specific Modbus master command (Command yy). A value of 1 (Occurrence) means the received data did not conform to the expected Modbus frame structure. This often points to baud rate or data format mismatches between the master and slave.
Modbus Master Command Parity Error
This boolean tag indicates that a parity error occurred during the communication of a specific Modbus master command (Command yy). A value of 1 (Occurrence) means a data transmission error was detected due to incorrect parity. This suggests corruption in the serial data stream, preventing reliable data exchange.
Modbus Master Command Response Timeout
This boolean tag indicates that the Modbus master did not receive a response from the slave device within the configured timeout period after sending a specific Modbus command (Command yy). A value of 1 (Occurrence) means the command failed to complete due to the slave's unresponsiveness. This can halt data exchange for that command.
Modbus Master Command Slave Error Code
This boolean tag indicates that the Modbus slave device returned an error code (distinct from an exception code) in response to a specific Modbus master command (Command yy). A value of 1 (Occurrence) means the slave device reported an internal issue or invalid request. This requires investigating the slave device's status or the command itself.
Modbus Master Command Data Uncertain
This boolean tag indicates that the data associated with a specific Modbus master command (Command yy) might be inaccurate, though the extent of the inaccuracy is not quantified. A value of 1 (Uncertain data) points to potential reliability issues with the command's data output. The tag automatically resets to 0 (Good data) once the condition causing uncertainty is removed.
Module Connection Fault
This boolean tag indicates if a connection between the module and its owner-controller is not running. A value of 1 signifies that the connection is faulted or not established. A value of 0 indicates the connection is running normally. This fault prevents the module from exchanging data with the controller.
Module Diagnostic Active / Prognostics Threshold Reached
This boolean tag indicates that one or more diagnostic conditions are currently active within the module, or a prognostics threshold has been reached. A value of 1 means active diagnostics are present, while 0 indicates no active diagnostics or prognostics thresholds. This suggests an underlying issue requiring further investigation to prevent potential system failure.
Modbus Master Channel Data Fault
This boolean tag indicates that the channel data for the Modbus master is inaccurate and cannot be trusted for use in the application. When set to 1 (Bad), it signifies an active fault condition within the module or its communication. The tag automatically resets to 0 (Good) once the underlying condition causing the inaccuracy is resolved.
Channel Operating State (Run)
This boolean tag indicates the operating state of a channel. A value of 1 signifies that the channel is in a Run state, actively processing or exchanging data. A value of 0 indicates the channel is Idle. While not a fault, an unexpected Idle state when Run is expected indicates a control system issue.
Modbus Master Channel Data Uncertain
This boolean tag indicates that the channel data for the Modbus master can be inaccurate, but the precise degree of inaccuracy is unknown. When set to 1 (Uncertain), it suggests potential issues with data integrity, though not a definitive fault. The tag automatically resets to 0 (Good data) once the condition causing uncertainty is removed.
Nonrecoverable Module Fault
The module status indicator displaying a steady red light signifies that the module has encountered a nonrecoverable fault. This type of fault prevents the module from operating normally and cannot be cleared without a module replacement if a power cycle is unsuccessful. This indicates a critical failure requiring immediate attention.