Cold Junction Open Wire (5069-IY4, 5069-IY4K)
Allen-Bradley · Compact 5000 I/O Analog Modules
Hva betyr CJChxx.OpenWire ?
This boolean tag indicates that the cold junction wire is disconnected from channel (xx) or the Removable Terminal Block (RTB) is removed from the module. A value of 1 signifies an open wire condition. This prevents accurate cold junction temperature readings.
Vanlige årsaker
- Cold junction signal wire disconnected from channel (CJChxx) terminals
- Removable Terminal Block (RTB) removed from the module
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Confirm that the cold junction signal wire is securely connected to the designated terminals of channel (CJChxx).
- 2
Verify that one of the compatible RTBs (5069-RTB14CJC-SPRING or 5069-RTB14CJC-SCREW) is correctly installed on the module.