CIPSyncTimeout

CIP Sync Master Timeout

Allen-Bradley · Compact 5000 Digital I/O Modules

Hva betyr CIPSyncTimeout ?

This boolean tag indicates that the module was previously synchronized with an IEEE 1588 master clock, but synchronization has been lost due to a timeout. A tag value of '1' means the module is now using its local clock and may drift from the last known synchronized time, potentially affecting time-critical operations.

Vanlige årsaker

  • Loss of network connection to the IEEE 1588 time master.
  • Failure or communication issues with the IEEE 1588 time master itself.
  • Network communication delays, congestion, or failures preventing CIP Sync updates to the module.
  • Module or time master CIP Sync configuration mismatch or error.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the presence and operational status of the IEEE 1588 time master device on the network.

  2. 2

    Check network connections and infrastructure (e.g., Ethernet cables, switches, routers) between the module and the time master for faults.

  3. 3

    Examine network traffic and module diagnostics for any communication issues related to CIP Sync in Studio 5000 Logix Designer.

  4. 4

    Ensure the module and time master have consistent and correct CIP Sync configuration settings in Studio 5000 Logix Designer.

Se alle koder i denne manualen (38)