This error is reported along with a Profile Code in the Mint WorkBench Error Log, which must be converted to hexadecimal to reveal the specific POWERLINK error code. This indicates that the POWERLINK master has received an error code from the drive.

Vanlige årsaker

  • An underlying POWERLINK-specific error reported by the drive to the master.
  • Incorrect POWERLINK network configuration or parameter settings.
  • Issues with POWERLINK communication cables, connectors, or network components.
  • Incompatibility between the POWERLINK master and the drive's POWERLINK implementation.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Connect to the drive with Mint Workbench and check the Error Log for the associated Profile Code.

  2. 2

    Convert the displayed Profile Code from decimal to hexadecimal format to identify the specific POWERLINK error code.

  3. 3

    Consult the POWERLINK specification or the drive's POWERLINK documentation for the meaning of the specific hexadecimal error code.

  4. 4

    Verify POWERLINK network cabling and connections for integrity, proper termination, and shielding.

  5. 5

    Check the POWERLINK configuration settings on both the master and the drive for consistency and correctness.