Current control loop is not tuned

ABB · Application Error ABB Motion Drives Error trouble shoo

Hva betyr 4068 ?

The current control loop has not been properly tuned before attempting rotor parameters autotuning, specifically applicable to asynchronous motors. Proper current loop tuning is a prerequisite for accurate rotor parameter identification.

Vanlige årsaker

  • Rotor parameters autotuning initiated before the current control loop was tuned.
  • Skipped or incomplete current loop tuning during the commissioning process.
  • Incorrect motor type selected, leading to an expectation of current loop tuning when it hasn't occurred.
  • Corruption of tuning parameters requiring a re-tune.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Re-run the full autotuning process, ensuring the current control loop tuning step is successfully completed first.

  2. 2

    Verify that the correct motor type (asynchronous motor) is selected in the drive parameters for which this tuning is applicable.

  3. 3

    Check drive diagnostics for any errors or warnings related to the current control loop tuning process itself.

  4. 4

    Ensure all motor nameplate data (e.g., current, voltage, speed) are accurately entered before starting autotuning.