247
Event not supported
ABB · Application Error ABB Motion Drives Error trouble shoo
Hva betyr 247 ?
The Mint program attempted to use an event that is not supported by the current controller hardware or firmware version (MotiFlex e100, MotiFlex e180, MicroFlex e190).
Vanlige årsaker
- Attempting to use an event that is not available on the specific controller model or its firmware version.
- Using an event that has been deprecated or changed in a newer firmware version without updating the program.
- The drive's hardware platform does not possess the necessary capabilities for the invoked event.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Amend the Mint program to use only events that are supported by the specific controller model and its current firmware version.
- 2
Consult the drive's firmware release notes or Mint programming manual to verify event compatibility for your hardware.
- 3
If possible, update the controller's firmware to a version that supports the desired event, or modify the program to use an alternative, supported event.
- 4
Review the error log for any additional information regarding the unsupported event.
Verifisert teknisk data. Sist oppdatert: March 2026