Output frequency over limit (_ecOUTPUT_FREQ_OVER_LIMIT)
ABB · Application Error ABB Motion Drives Error trouble shoo
Hva betyr 10041 ?
The drive has detected that its output frequency exceeded 550 Hz. This restriction is implemented to comply with relevant European Export Control Regulations, indicating an attempt to operate beyond a regulatory limit.
Vanlige årsaker
- Commanded speed or frequency exceeding the regulatory limit of 550 Hz.
- Incorrect scaling or gear ratio parameters leading to an excessively high calculated output frequency.
- Drive parameters related to maximum frequency set above the regulatory threshold.
- External control system commanding an output frequency beyond the drive's legal limit.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Review the application's speed requirements and ensure that the commanded frequency does not exceed 550 Hz.
- 2
Check drive parameters related to maximum output frequency and adjust them to be below or equal to 550 Hz.
- 3
Verify scaling factors, gear ratios, and other motion parameters to ensure accurate calculation of output frequency.
- 4
Examine the external control system (e.g., PLC, HMI) to ensure it is not issuing commands that result in exceeding the 550 Hz limit.