10038

Encoder battery dead

ABB · Application Error ABB Motion Drives Error trouble shoo

Hva betyr 10038 ?

This informational message can appear at startup or when the drive (MotiFlex e100, MotiFlex e180, MicroFlex e190) is enabled, indicating that the battery backup supply for a Smart Abs encoder has failed or is depleted.

Vanlige årsaker

  • The battery in the Smart Abs encoder has reached the end of its service life and is exhausted.
  • Poor contact or corrosion at the battery terminals, preventing proper power delivery.
  • The battery is missing or incorrectly installed in the Smart Abs encoder.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Replace the battery in the Smart Abs encoder with a new, compatible battery according to the encoder's specific manual and manufacturer guidelines.

  2. 2

    Verify that the new battery is correctly installed and that its connections are secure and free from corrosion.

  3. 3

    Check for any error messages related to the encoder after battery replacement to confirm the issue is resolved and position data is retained.

  4. 4

    Record the battery replacement date for future maintenance planning.