Encoder not ready to operate
ABB · Application Error ABB Motion Drives Error trouble shoo
Hva betyr 10028 ?
The drive (MotiFlex e100, MotiFlex e180, MicroFlex e190) is configured to use a Serial Encoder but is unable to provide position information. This error is generated if an attempt is made to enable the axis before the encoder is ready (which can take several seconds) or if the resolution configured on the drive is not compatible with the encoder. The axis will be crash stopped and disabled.
Vanlige årsaker
- Attempt to enable the axis before the serial encoder has completed its readiness sequence.
- The encoder resolution configured on the drive is not compatible with the connected serial encoder.
- An internal fault within the encoder preventing it from providing valid position information.
- Wiring issues or poor connections for the serial encoder.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Allow several seconds for the serial encoder to become ready after power-up before attempting to enable the axis.
- 2
Verify that the encoder resolution configured in the drive's parameters matches the specifications of the connected serial encoder.
- 3
Connect to the drive with Mint Workbench, navigate to "Parameters > Encoder > Channel 0 > Encoder Parameter(Encoder0, Fault Register)", and check for a non-zero value. Consult the help file subject "ENCODERPARAMETER" for specific fault details.
- 4
Inspect all encoder wiring and connections for integrity, proper shielding, and secure termination according to the installation manual.