EXTERNAL FLT

ABB · ACS800

Hva betyr 9000 ?

A fault condition has been reported by an external device connected to the ABB ACS800 drive. This information is typically transmitted via a programmable digital input to the drive. This protection is linked to programmable Fault Function 30.03.

Vanlige årsaker

  • An actual fault condition in an external device (e.g., external overload relay trip, safety gate open, pressure switch activation).
  • Incorrect configuration of parameter 30.03 (EXTERNAL FAULT), leading to misinterpretation of the digital input signal.
  • Wiring issue on the digital input used for external fault monitoring (e.g., loose connection, broken wire, incorrect voltage level).
  • External device fault contact chattering or intermittent operation.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check all external devices connected to the drive's digital inputs for faults and resolve any issues (e.g., reset external overloads, close safety gates).

  2. 2

    Verify parameter 30.03 (EXTERNAL FAULT) setting to ensure the correct digital input is selected and the fault logic (normally open/closed) matches the external device.

  3. 3

    Check the wiring of the digital input associated with the external fault for continuity, secure connections, and correct voltage level (e.g., 24VDC) when the external device is healthy.

  4. 4

    Clear the fault on the external device before attempting to reset the drive.