Fan is not operating correctly (_ecFAN_LOSS)
ABB · ACS850 Standard Program Firmware
Hva betyr 30010 ?
The drive has detected a failure of its internal cooling fan. This means the drive is not being adequately cooled, and continued operation risks severe over-temperature conditions, leading to damage to internal components.
Vanlige årsaker
- Fan motor seized or bearings worn out, preventing rotation.
- Fan power supply (e.g., 24VDC) on the drive's control board has failed.
- Fan control circuit or sensor on the drive's main board is malfunctioning.
- Accumulation of dust and debris on fan blades, increasing friction and impeding rotation.
- Loose or disconnected fan wiring harness inside the drive.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Power down the drive and visually inspect the fan blades for physical obstructions or damage.
- 2
2. Gently try to rotate the fan blades manually (with power off) to check for seizure or excessive resistance.
- 3
3. Verify the fan's electrical connection to the drive's control board is secure and free from corrosion.
- 4
4. With the drive powered on (and fault cleared if possible), observe if the fan spins during operation or when commanded (if controllable).
- 5
5. Measure the voltage at the fan's terminals on the control board (if accessible and safe) to confirm power supply.
- 6
6. Replace the internal cooling fan if visual inspection or power checks indicate mechanical or electrical failure of the fan unit itself.