Oversetter...
10035

STO input mismatch (_ecSTO_INPUT_MISMATCH)

ABB · ACS850 Standard Program Firmware

Hva betyr 10035 ?

The drive has detected an inconsistency in its internal Safe Torque Off (STO) registers, meaning the two redundant STO inputs are not in the same state. This is a safety fault that can occur whether the drive is enabled or disabled, indicating a potential failure in the safety circuit or a timing issue, which compromises the STO function.

Vanlige årsaker

  • One of the two redundant STO input signals (e.g., STO_IN1, STO_IN2) transitions state (e.g., from 24VDC to 0VDC) significantly before or after the other.
  • Asynchronous operation of external safety relays or contacts supplying the two STO inputs, leading to a momentary state difference.
  • A wiring fault or intermittent connection on only one of the STO input terminals (e.g., a loose wire at X12.1 but not X12.2).
  • Interference (e.g., EMI) affecting only one of the STO input signal lines, causing a momentary false transition.
  • Internal timing discrepancy or component tolerance drift within the STO monitoring circuit of the drive.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Using a dual-channel oscilloscope, monitor both STO input signals (e.g., STO_IN1 at X12.1 and STO_IN2 at X12.2) simultaneously to identify any timing discrepancies during state changes.

  2. 2

    Inspect the wiring to both STO input terminals (e.g., X12.1 and X12.2) for any loose connections, damaged insulation, or incorrect termination.

  3. 3

    Test the external safety relays or contactors (e.g., K1, K2) providing the STO signals for consistent and simultaneous opening/closing of their contacts.

  4. 4

    Ensure adequate shielding for the STO input cables, and route them away from power cables or sources of high electromagnetic interference (EMI).

  5. 5

    Confirm that the drive's STO configuration parameters (if any, e.g., P10-01 (STO Delay Time)) are set appropriately for the application and safety component response times.

Se alle koder i denne manualen (57)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: ABB ACS850 Standard Program Firmware