Oversetter...
8110
Analog Input Below Minimum
ABB · ACS800 Standard Firmware
Hva betyr 8110 ?
An analog input signal (e.g., 0-10V, 4-20mA) has fallen below its configured minimum limit, which must be set to 0.5V (1 mA) or above in parameter group 13. Depending on parameter 30.01 (AI<MIN FUNCTION), the drive may trip, set a constant speed (12.16), or freeze at the last operating speed.
Vanlige årsaker
- Analog input signal (e.g., AI1, AI2) is below its configured minimum threshold (P7-01, P7-02).
- Sensor failure providing a reading outside expected operational range.
- Incorrect calibration of the analog input signal.
- Wiring issue or short circuit on the analog input line.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify parameter 30.01 (AI<MIN FUNCTION) is set correctly for the desired drive reaction upon signal loss.
- 2
Measure the analog input signal at its respective terminals (e.g., AI1, AI2) to confirm it is above the set minimum limit.
- 3
Review parameter settings in group 13 (ANALOGUE INPUTS) to confirm the minimum limit is configured correctly, typically 0.5V (1mA) or above.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: ABB ACS800 Standard Firmware