4313

Motor 2 Temperature Alarm

ABB · ACS800 Standard Firmware

Hva betyr 4313 ?

The measured temperature of motor 2 has exceeded the alarm limit set by parameter 35.05. This indicates a potential overheating condition specific to motor 2, requiring attention to prevent damage.

Vanlige årsaker

  • Temperature alarm threshold reached for Motor 2.
  • Motor 2 experiencing excessive heat.
  • Faulty temperature sensor on Motor 2.
  • Overload or inadequate cooling for Motor 2.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the alarm limit value set in parameter 35.05 to ensure it is appropriate for the motor.

  2. 2

    Verify that the actual number of temperature sensors connected to motor 2 corresponds to the value set by the parameter.

  3. 3

    Stop motor 2 and allow it to cool down to a safe operating temperature.

  4. 4

    Ensure proper cooling for motor 2 by checking its cooling fan for operation and cleaning any cooling surfaces.

Se alle koder i denne manualen (33)
Verifisert teknisk data. Sist oppdatert: March 2026