Safe torque off 2
ABB · ACS580
Hva betyr FA82 ?
An asymmetric loss of one of the Safe Torque Off (STO) signals has occurred (e.g., IN2 lost while IN1 is present). This is interpreted as a malfunction in the safety circuit and causes the drive to trip. The drive will not start until both STO signals are restored and all related faults are reset.
Vanlige årsaker
- Open circuit or wiring break specifically affecting the STO IN2 input signal cable.
- Faulty safety relay or PLC output module that controls STO IN2, causing it to drop out independently.
- Loose connection or faulty terminal (e.g., STO_IN2 terminal) on the drive's safety board.
- Internal component failure on the drive's STO circuit for the IN2 channel.
- Incorrect voltage level on STO IN2 (e.g., below 18VDC) while STO IN1 remains high (e.g., 24VDC).
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
De-energize the drive. Measure continuity of the STO IN2 cable conductor from the safety source (relay/PLC) to the drive's STO IN2 terminal.
- 2
Measure voltage across the STO IN2 terminal (e.g., X2) relative to common (e.g., X3) with the safety function engaged; expect 24VDC.
- 3
Verify the output status of the safety relay or PLC module driving STO IN2, ensuring it provides a consistent signal when active.
- 4
Inspect the wiring at the drive's STO IN2 terminal (e.g., X2) for loose connections, damage, or corrosion.
- 5
If a separate safety module is used, check its diagnostic LEDs or software status for faults related to STO channel 2.