Oversetter...
FF89

MOD CHOKE T

ABB · ACS560 Standard Control Program Firmware

Hva betyr FF89 ?

Overtemperature has occurred in the choke of a liquid-cooled R8i inverter module. Excessive heat in the choke can reduce its magnetic properties and potentially lead to insulation breakdown, compromising drive performance and safety.

Vanlige årsaker

  • Insufficient flow rate or incorrect temperature of the cooling liquid circulating through the R8i module's choke cooling jacket.
  • Partial or complete blockage in the cooling liquid circuit (e.g., filter clog, pump failure) reducing heat removal from the choke.
  • Accumulation of scale or debris within the choke's liquid cooling channels, impairing heat transfer efficiency.
  • Sustained operation above the choke's rated current (e.g., due to motor overload or short circuit conditions).
  • Faulty temperature sensor (thermistor/PT100) providing an inaccurate reading from the choke.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Verify the cooling liquid flow rate (e.g., liters/minute) to the R8i module and compare it to the drive's specified minimum flow.

  2. 2

    2. Measure the temperature of the cooling liquid entering and exiting the R8i module's cooling circuit, checking for expected differential.

  3. 3

    3. Inspect the cooling liquid filters for clogging and clean or replace as required, then check for pump operation.

  4. 4

    4. Monitor the motor current (P1-15) and drive output current (P1-16) to ensure they are within the choke's continuous current rating.

  5. 5

    5. Measure the resistance of the choke temperature sensor and compare it to the sensor's temperature-resistance curve to confirm accuracy.

Se alle koder i denne manualen (33)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: ABB ACS560 Standard Control Program Firmware