Mitsubishi Electric FR-D700

61 fault codes documented

Analog input fault

Analog Input Fault

A voltage (or current) has been input to terminal 4 when the setting in Pr. 267 Terminal 4 input selection and the physical voltage/current input switch on the inverter are mismatched. This incorrect input configuration can lead to erroneous frequency commands, unstable operation, or potentially damage the analog input circuit if not corrected.

Calibration error

Calibration Error

The analog input bias and gain calibration values (C3, C4, C6, C7) have been set too close, potentially causing instability, inaccuracy, or an invalid range in analog input readings. This can lead to incorrect frequency commands or control signals, affecting system performance. The inverter output is not shut off.

CPU fault

CPU Fault

An error has occurred within the inverter's Central Processing Unit (CPU) or its associated peripheral circuits. This is a critical internal hardware or software issue, potentially leading to a complete loss of control and unpredictable inverter behavior. Continued operation or neglect may result in further hardware damage or system unresponsiveness.

E.CPU

Internal Safety Circuit Fault (CPU)

This fault code signifies a detected malfunction within the inverter's internal safety circuit, specifically indicating an issue related to the CPU's safety monitoring functions. When triggered, it causes the inverter to shut off its output to maintain a safe state and prevent motor operation.

E.OC1

Overcurrent Trip During Acceleration

An excessive current condition has been detected while the inverter is accelerating the motor. This can be caused by an abnormally high load, a short circuit between phases, or a ground fault on the inverter's output side, potentially leading to damage if not resolved.

E.SAF

Internal Safety Circuit Fault

This fault code indicates a detected malfunction within the inverter's internal safety circuit. When active, it causes the inverter to shut off its output to ensure a safe state, preventing drive operation. This is a critical internal error.

E14

Master/Slave System Control Wiring Error / SW Setting Error

This indicates an incorrect setting of DIP switches (SWS) on the indoor unit PCB when configuring a master/slave system. It also points to incorrect control wiring or an open circuit in the control wiring between master and slave units.

E16

Faulty Indoor Fan Motor

The indoor fan motor is faulty, preventing proper air circulation. This can lead to inefficient cooling/heating or system shutdown.

E28

Remote Controller Sensor Failure

The sensor within the remote controller has failed, leading to incorrect temperature or operational readings. This affects the indoor unit's ability to control room temperature accurately.

E30

Indoor/Outdoor Unit Connected Error

This error indicates a problem with the connection or communication between the indoor and outdoor units. It prevents proper system operation and coordination.

E31

Indoor/Outdoor Unit Address Setting Error (Duplication)

There is a duplication of an indoor unit address number within the U00-U47 range, or an outdoor unit address setting error has occurred. This conflict prevents proper system communication and unit identification.

E32

Mains Power Phase Reversal / Open Phase Detection

The anti-phase device has detected that two phases of the mains power need to be swapped, indicating a phase reversal. Alternatively, the L2 phase of the mains power (primary side of contactor) has been detected as open, leading to unbalanced power.

E34

Abnormally Low Current / L3 Open Phase

Abnormally low current or no current has been detected by the current transformer (CT) on L3. This indicates an open phase condition detected at L3 (secondary side of contactor), which can prevent the compressor from operating correctly.

E35

Outdoor Unit Heat Exchanger Sensor (ThOR) Defective / Cooling High Pressure

The outdoor unit heat exchanger sensor (ThOR) is defective, indicated by an open or closed circuit resistance, or by a poor connection of the sensor connector on the outdoor unit PCB. This can also be caused by high pressure in the cooling system, impacting heat exchange.

E36

Abnormally High Discharge Temperature / Insufficient Refrigerant / THOD Defective

The compressor discharge temperature is abnormally high. This can be caused by insufficient refrigerant, a defective compressor discharge temperature sensor (THOD), or other system issues leading to compressor overheating and potential damage.

E37

Outdoor Unit Heat Exchanger Sensor (ThOR) Defective / Poor Connection

The outdoor unit heat exchanger sensor (ThOR) is defective (open circuit resistance) or has a poor connection on the outdoor unit PCB. This error may also specify which particular thermistor (Tho-R1 to Tho-R6) has failed, leading to inaccurate temperature readings.

E38

Outside Air Temperature Sensor (ThoA) Defective / Poor Connection

The outside air temperature sensor (ThoA) is defective (open circuit resistance) or has a poor connection on the outdoor unit PCB. This compromises the system's ability to accurately sense ambient conditions and adjust operation.

E39

Compressor Discharge Temperature Sensor (ThOD) Defective / Poor Connection

The compressor discharge temperature sensor (ThOD) is defective (open circuit resistance) or has a poor connection on the outdoor unit PCB. This can lead to incorrect discharge temperature monitoring, potentially causing compressor damage.

E40

High-Pressure Switch Tripped / System Overcharge / Service Valves Closed / Insufficient Airflow

The high-pressure switch (B3H or 63H1) has tripped. This can be caused by a system overcharged with refrigerant, one or more service valves being shut, or insufficient airflow over the condenser coil, all leading to dangerously high system pressures.

E41

Inverter Power Transistor Overheat

The power transistor for the inverter has overheated, indicating excessive heat generation, potentially due to a fault or overload condition. This poses a risk to the inverter module's longevity.

E42

Abnormally High Compressor Current

Abnormally high current has been detected in the compressor, indicating a potential electrical or mechanical fault with the compressor, or system overload. This can lead to compressor failure if not addressed.

E43

Exceeded Maximum Number of Indoor Units

The maximum allowed number of indoor units connected to one outdoor unit has been exceeded, or an outdoor unit has reached its capacity limit. This leads to system communication issues and operational faults.

E45

Transmission Error / Loose Connection (Cal)

A transmission error has occurred between the inverter and the outdoor unit PCB, possibly due to a loose connection at the 'Cal' terminal. This disrupts critical communication and control signals.

E46

Address Setting Conflict

There is a conflict of address settings, where a combination of automatic, manual, or remote control addresses coexist on the same network. This prevents proper system addressing and communication.

E47

Inverter Overvoltage

The inverter has detected an overvoltage condition, which could be due to an unstable power supply or a malfunction within the inverter itself. This protects the inverter components from damage.

E48

DC Outdoor Fan Motor Fault

There is a fault with the DC outdoor fan motor, which could prevent proper heat exchange in the outdoor unit. This leads to inefficient operation and potential system overheating.

E49

Low Pressure / Voltage Detected / Inverter PCB Fault

This fault indicates a low pressure condition, low voltage detected within the system, or an inverter PCB fault. The manual lists these three distinct sub-causes for E49, any of which can lead to system malfunction.

E51

Power Transistor Overheat

The power transistor has overheated, indicating excessive heat generation, potentially due to a fault or overload condition. This protects the inverter from damage.

E53

Suction Pipe Thermistor (Tho-S) Disconnected

The suction pipe thermistor (Tho-S) is disconnected, which will prevent accurate temperature readings for the suction line. This compromises the system's ability to regulate superheat and optimize refrigerant flow.

E54

Low/High Pressure Sensor Disconnection/Output Error

This error indicates a disconnection or output error with either the low-pressure sensor (PSL) (E54-1) or the high-pressure sensor (PSH) (E54-2). This prevents accurate pressure monitoring, jeopardizing system safety and control.

E55

Compressor Under Dome Thermistor Disconnected

The thermistor located under the compressor dome is disconnected, which will prevent critical temperature monitoring of the compressor shell. This can lead to undetected compressor overheating and failure.

E56

Power Transistor Thermistor Faulty or Disconnected

The power transistor thermistor is faulty or disconnected (specific to FDCVA151-251 models), impacting temperature monitoring of the power transistors. This can lead to inverter damage from overheating.

E57

Refrigerant Leak / Shortage

This indicates a refrigerant leak or shortage of refrigerant (specific to FDCVA151-251 models), leading to insufficient cooling or heating performance. A low refrigerant charge can cause compressor overheating and damage.

E59

Compressor Start-up Error

The compressor has failed to start properly, which can be due to electrical issues, mechanical binding, or control problems. This prevents the system from generating cooling or heating capacity.

E60

Compressor Position Detection Error

An error has occurred in detecting the compressor's rotational position, which is critical for proper inverter control. This can prevent the compressor from starting or running smoothly, leading to system shutdown.

E83

Emergency Stop of Indoor Unit

The indoor unit has initiated an emergency stop, indicating a critical safety or operational fault. This requires immediate attention to prevent further damage or unsafe conditions.

E112

Unit Address Conflict (Factory Setting) / Auto Address Not Possible

One or more units (indoor or outdoor) are still addressed at 48 or 49 (factory setting). This prevents auto-addressing, which is only possible on a single KX2 system, if one or more units (either indoor or outdoor) are not set at 49.

Electronic thermal relay function pre-alarm

Electronic Thermal Relay Function Pre-Alarm

The cumulative thermal value of the electronic thermal O/L relay has reached 85% or higher of the Pr. 9 (Electronic thermal O/L relay) setting. This indicates that the motor or inverter is approaching its thermal overload limit. Continuing operation without intervention will almost certainly lead to an electronic thermal overload trip, shutting down the inverter.

External thermal relay operation

External Thermal Relay Operation

The external thermal relay connected to the OH signal has been activated. This indicates that the motor or connected equipment is experiencing an overload condition, potentially causing damage if not addressed. The inverter will not restart unless it is manually reset after the relay contacts return to normal.

Fan alarm

Fan Alarm

The cooling fan is either at a standstill despite being required to operate, or its speed has significantly decelerated, indicating a malfunction. The cooling fan is essential for dissipating heat from the inverter. Without adequate cooling, the inverter will overheat and trip, potentially leading to irreversible component damage.

Inrush current limit circuit fault

Inrush Current Limit Circuit Fault

The resistor of the inverter's inrush current limit circuit has overheated. This typically occurs due to frequent power cycling (ON/OFF) of the inverter, which causes the inrush current limiting components to work excessively, leading to thermal stress and potential failure. Overheating can degrade or destroy these components, preventing proper inverter startup.

Inverter reset

Inverter Reset

The reset signal (RES signal) is ON, causing the inverter to immediately shut off its output. This indicates that a reset command has been issued, either manually through a control signal or automatically by the system, placing the inverter in a non-operational state.

Maintenance signal output

Maintenance Signal Output

The cumulative energization time of the inverter has exceeded the set value in the maintenance output timer (Pr. 503). This is a reminder or pre-alarm indicating that periodic maintenance is due, based on accumulated operational hours. It is not a fault but a preventative warning, suggesting that routine checks are required.

Mode designation error

Mode Designation Error

Parameter setting was attempted in External or NET operation mode when Pr. 77 (Parameter write selection) was not '2', or parameter writing was attempted when the command source was not the operation panel. This prevents modification of parameters under specific operating conditions to maintain system integrity and prevent unintended changes.

Operation panel lock

Operation Panel Lock

An attempt was made to operate the inverter while the operation panel was in a locked state, preventing parameter changes or control actions. This is often a security or accidental lockout feature designed to prevent unauthorized modifications. The inverter will not respond to panel inputs until unlocked.

Output current detection value exceeded

Output Current Detection Value Exceeded

The output current has exceeded the detection level set in a parameter. This functions as a protective measure to prevent overcurrent conditions that could damage the motor or the inverter's power components. Incorrect parameter settings can trigger this unnecessarily, or it could indicate an actual motor overload or short circuit condition.

Parameter storage device fault

Parameter Storage Device Fault

The component responsible for storing parameters (typically on the control circuit board) has become abnormal, indicating a potential hardware or firmware issue. This fault can lead to incorrect operation, loss of configured settings, or general system instability. Unresolved, it risks unpredictable behavior or complete system failure.

Password locked

Password Locked

An attempt was made to read or write a parameter that is restricted by a password, preventing access or modification. This security feature protects critical parameters from unauthorized changes, ensuring system integrity and safety. Access is denied until the correct password is provided.

PTC thermistor operation

PTC Thermistor Operation

The resistance of the PTC thermistor, connected between terminals 2 and 10, has exceeded the set protection level (Pr. 561). This signifies that the monitored motor or component is overheating. Continuing operation under this condition poses a high risk of severe motor damage.

PU disconnection

PU Disconnection

A communication error has occurred between the PU (Parameter Unit) and the inverter, or the communication interval has exceeded the permissible time during RS-485 communication. This also triggers if the number of communication errors exceeds the retry limit. Loss of communication means the inverter cannot receive commands or send status, interrupting operation.

PU stop

Parameter Unit (PU) Stop

The [STOP] key on the operation panel of the Parameter Unit (PU) was pressed during External operation. This indicates a manual stop command was initiated from the PU while the inverter was configured for external control, causing the inverter to cease operation.

Regenerative brake pre-alarm

Regenerative Brake Pre-Alarm

The regenerative brake duty cycle has reached 85% or higher of the Pr. 70 (Special regenerative brake duty) setting. This is a warning that the inverter's regenerative braking capacity is nearing its thermal limit. Continuous operation at this level can lead to an overvoltage fault, damage to internal components, or overheating of the braking resistor if one is installed.

Retry count excess

Retry Count Excess

The inverter has failed to restart within the set number of retries after a preceding error or trip. This indicates a persistent underlying problem that the inverter's automatic recovery attempts could not resolve, requiring manual intervention to prevent further issues.

SA

Safety Stop Mode (S1/S2 Open)

This alarm indicates that both safety input signals (S1 and S2) are in an open state, which triggers the safety stop function and causes the inverter output to shut off. This typically occurs as an intended safety action or due to a wiring issue, not an internal safety circuit fault.

Safety circuit fault

Safety Circuit Fault (Input Open)

This fault occurs when the safety circuit input terminals (across S1 and PC, or across S2 and PC) are detected as open. This indicates a break in the safety loop, signaling a potentially unsafe condition and leading to inverter shutdown. It could be due to incorrect wiring, a fault in an external safety device, or an activated safety interlock.

Safety Stop

Safety Stop

The safety stop function has been activated, resulting in an immediate shutdown of the inverter outputs. This critical safety measure is typically triggered by an external safety device or a wiring issue across terminals S1 and SC, or S2 and SC, indicating an open circuit in the safety chain. If misconfigured or experiencing an internal failure, it can prevent normal operation or compromise machinery safety.

Stall prevention (overcurrent)

Stall Prevention (Overcurrent)

The overcurrent stall prevention function has been activated. This warning indicates that the motor is encountering excessive current, possibly due to overload, insufficient acceleration time, improper torque boost settings, or mechanical binding. While a warning, prolonged activation can lead to motor or inverter damage.

Stall prevention (overvoltage)

Stall Prevention (Overvoltage)

The overvoltage stall prevention function has been activated, often during regeneration avoidance operation. This warning indicates that the DC bus voltage is exceeding safe limits, typically due to rapid deceleration or regenerative loads feeding energy back into the inverter. Sustained overvoltage can damage the inverter's internal components.

Undervoltage

Undervoltage

The voltage at the main circuit power supply has dropped below an acceptable operating level. This can be caused by issues in the power supply line, such as voltage sags, power supply capacity problems, or faulty connections. Sustained undervoltage can lead to unreliable inverter operation, internal component stress, or even damage.

Write disable error

Write Disable Error

This error occurs when parameter writing is set to be disabled (via Pr. 77 Parameter write selection), when frequency jump ranges (Pr. 31 to Pr. 36) overlap, or when normal communication between the PU and inverter cannot be established. It prevents new parameter settings from being applied, potentially leading to incorrect operation if desired changes are not accepted.

Write error during operation

Write Error During Operation

Parameter writing has been attempted while the inverter is actively operating (STF/STR signal is ON) and Pr. 77 Parameter write selection is not set to '2'. This error prevents parameter changes from being applied while the motor is running, which could cause instability, unsafe conditions, or unexpected behavior if allowed.