U5

Abnormal Heatsink Temperature

Mitsubishi Electric · Mitsubishi PUZ-HA30-36NHA4 Outdoor Unit

What does U5 mean?

The heatsink thermistor (TH8) detects an abnormal temperature, either too low (below -40°F [-40°C]) or too high (above 183°F [84°C]). This indicates a potential issue with the outdoor fan, restricted airflow, excessive ambient temperature (above 114°F [46°C]), or a fault in the thermistor or associated circuit boards.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Verify the ambient temperature around the outdoor unit to ensure it is within the specified operating limits (e.g., upper limit 114°F [46°C]).

  2. 4

    Measure the resistance value of thermistor TH8 and compare it to expected values for the measured temperature.

  3. 5

    If the outdoor fan, airflow, and thermistor are confirmed normal, replace the outdoor power circuit board.

  4. 6

    If fan drive is faulty, replace the outdoor controller circuit board.

Source: Mitsubishi PUZ-HA30-36NHA4 Outdoor Unit
Open Manual (Page 27)