E.USB
USB Communication Fault
Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
What does E.USB mean?
The inverter output has shut off because USB communication was interrupted for a duration exceeding the time set in Pr.548 USB communication check time interval. This indicates a break in the USB connection or an incorrectly configured communication watchdog timer. Loss of communication will prevent external control and monitoring.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If intermittent disconnections are expected or tolerated, increase the Pr.548 setting or set it to "9999" to disable the communication check.
Source: Mitsubishi FR-E800 Variable Frequency Drive