E.PID
PID Signal Fault
Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
What does E.PID mean?
The inverter output is shut off if, during PID control, the measured feedback value goes outside the limits set by Pr.131 (PID upper limit) or Pr.132 (PID lower limit), or if the absolute deviation from the setpoint exceeds Pr.553 (PID deviation limit). This protective function is not active by default and must be enabled via Pr.554. An erroneous PID signal can lead to unstable process control or unexpected shutdowns, indicating a sensor issue or incorrect parameter tuning.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If the function is intended to be active, confirm that Pr.554 (PID signal operation selection) is enabled and configured appropriately.
Source: Mitsubishi FR-E800 Variable Frequency Drive