U3

Discharge Thermistor Short/Open

Mitsubishi Electric · R410A Systems

What does U3 mean?

The compressor discharge thermistor, which monitors compressor discharge temperature, is detected as either short-circuited or open-circuited. This prevents accurate temperature measurement and compromises the system's ability to protect the compressor from overheating.

Repair Steps

  1. 1

    Measure the resistance of the discharge thermistor at its leads — compare to a resistance-temperature chart if available.

  2. 2

    Inspect the thermistor's wiring and connector on the outdoor unit PCB for damage, corrosion, or secure seating.

  3. 3

    Verify the thermistor is correctly seated and making good thermal contact with the compressor discharge pipe.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026
Source: Mitsubishi Electric R410A Systems