F2
L3 Open Phase Detection
Mitsubishi Electric · R410A Systems
What does F2 mean?
The outdoor unit has detected an open circuit in the L3 phase of the main power supply. This indicates a loss of one of the three input phases, potentially leading to unbalanced operation or motor damage.
Repair Steps
- 1
Measure voltage between L1-L2, L2-L3, and L3-L1 at the outdoor unit main power terminals — expect balanced 3-phase voltage.
- 2
Inspect all wiring connections for the L3 phase at the outdoor unit's main power terminals for looseness or corrosion.
- 3
Check the integrity of the circuit breaker or fuse protecting the L3 phase in the electrical panel.
Verified technical data. Last updated: March 2026
Source: Mitsubishi Electric R410A Systems