E42
Compressor Abnormally High Current
Mitsubishi Electric · R410A Systems
What does E42 mean?
The system has detected an abnormally high current draw by the compressor. This indicates an overload condition, potentially due to mechanical issues, excessively high head pressure, or an electrical fault within the compressor motor.
Repair Steps
- 1
Measure compressor running current on all three phases using a clamp meter — compare to the motor nameplate FLA.
- 2
Measure discharge and suction pressures to check for high head pressure or liquid slugging.
- 3
Measure winding resistance of the compressor motor phases (U-V, V-W, U-W) and to ground using an ohmmeter.
Verified technical data. Last updated: March 2026
Source: Mitsubishi Electric R410A Systems