E40
High-Pressure Switch Trip
Mitsubishi Electric · R410A Systems
What does E40 mean?
The high-pressure switch (B3H or 63H1) has tripped. Common causes include system overcharge, one or more service valves being shut, or insufficient airflow over the condenser coil, all leading to excessively high head pressure.
Repair Steps
- 1
Measure system high-side pressure using manifold gauges.
- 2
Check refrigerant charge using manifold gauges and subcooling calculations — evacuate and recharge with the precise amount if overcharged.
- 3
Inspect all service valves in the liquid and suction lines — verify they are fully open.
- 4
Verify condenser coil cleanliness and unrestricted airflow; check outdoor fan motor operation and fan blade integrity.
Verified technical data. Last updated: March 2026
Source: Mitsubishi Electric R410A Systems