E38
Outside Air Temperature Sensor (ThOA) Defective
Mitsubishi Electric · R410A Systems
What does E38 mean?
The outdoor ambient air temperature sensor (ThOA) is defective (resistance is open circuit) or has a poor connection to the outdoor unit PCB. This impacts the system's ability to adjust operation based on ambient conditions, affecting efficiency.
Repair Steps
- 1
Measure the resistance of the ThOA sensor at its leads — compare to a resistance-temperature chart if available.
- 2
Inspect the ThOA sensor's connector on the outdoor unit PCB — verify it is securely seated and free from corrosion.
- 3
Check for damage to the sensor wiring between the sensor and the PCB using a multimeter for continuity.
Verified technical data. Last updated: March 2026
Source: Mitsubishi Electric R410A Systems