E.OP1 to OP3
Option slot alarm
Mitsubishi Electric · Mitsubishi A500 Inverter
What does E.OP1 to OP3 mean?
The inverter output is stopped if a functional alarm occurs in the plug-in option loaded in the corresponding slot (1, 2, or 3). This can include a communication alarm for a communication option or a contact fault for other types of plug-in options.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check the communication cable connected to the option for wire breakage or loose connections.
- 4
Verify that the termination resistor (if required for the specific option) is correctly fitted and configured.
Source: Mitsubishi A500 Inverter