UL
Abnormal low pressure (Low-pressure switch activated)
Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
What does UL mean?
The 63L low-pressure switch activates, indicating system pressure below -0.07 MPa (-10 PSIG) during compressor operation. This critical fault suggests a closed outdoor unit stop valve, significant refrigerant leakage/shortage, or a malfunction in the linear expansion valve. Ignoring this can lead to severe and irreparable damage to the compressor.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check the system for refrigerant leakage and correct the refrigerant amount to the proper level.
- 4
Inspect and test the linear expansion valve for proper operation. Refer to Section 10-6.
- 5
If all other components are confirmed functional, replace the outdoor controller board.
Source: Mitsubishi Electric PUZ-HA30/36NHA4 Outdoor Unit
View Official PDF